Overhead insulated cables with rated voltage 1KV and below
Key words:
Category:
Control Cable

Consult:
Overhead insulated cables with rated voltage 1KV and below
use
This product is suitable for copper core, aluminum core or aluminum alloy core weather-resistant polyvinyl chloride (referred to as PVC), polyethylene (referred to as PE) and cross-linked poly Ethylene (abbreviated as XLPE) insulated overhead cable.
Applicable conditions
1. The rated voltage U0/U is 0.6/1KV.
2. The long-term allowable working temperature of cable conductors: PVC and polyethylene insulation should not exceed 70 °C; XLPE insulation should not exceed 90 °C.
3. The laying temperature of the cable shall not be lower than -20℃.
4. The allowable bending radius of the cable: if the cable outer diameter (D) is less than 25mm, it should not be less than 4D; if the cable outer diameter (D) is 25mm and above, it should not be less than 6D.